(Tianjin Huigao Magnetics Co.,Ltd)The selection of the lamination type for a specific transformer depends on the design parameters and the designer’s personal preferences. We hold UL insulation system for Class B(130℃),F(155℃),H(180℃). We can make customized lamination transformers.
Power Capacity Chart
|
Power range (W)
|
Imperial Type Laminations
|
Metric Type Laminations
|
|
<5
|
306, 212
|
EI28, EI30, EI38, EI35, EI41
|
|
5-10
|
212
|
EI41, EI48
|
|
10-20
|
212, 130, 120
|
EI48, EI54
|
|
20-50
|
120, 279, 43
|
EI54, EI57, EI66
|
|
50-100
|
279, 43, 174
|
EI66, EI76
|
|
100-200
|
174, 173
|
EI96, EI105, EI114
|
|
200-500
|
173, 180
|
EI114, EI133
|
|
500-1000
|
180, P
|
EI133, EI150
|
|
>1000
|
Q, S
|
EI171
|
Note: The power capacity of each lamination type varies due to differences in size, thickness, operating frequency and temperature, flux density, and material grade. Chart calculated using 50CS400 grade steel or equivalent laminations.